Strobes must be located within 15 feet of either end of a hallway.
Fire alarm strobe dimensions.
If there are 1000 plus rooms there should be 20 fire alarm strobe equipped rooms plus 1 additional equipped room for each 100 over 1000.
If a corridor turns it must have strobe lights at each end so they can be seen from either direction.
Design install a fire alarm in houston tx.
Rianbottle fire alarm siren strobe alarm siiren horn home security safe system for house office hotel etc first aid emergency situation 4 3 out of 5 stars 8 13 99 13.
It also makes a ground fault more likely solid is a standard job spec in this area for fire alarm conductors i don t know why.
6 where the ceiling strobe is not located in the center of the room the candela level shall be determined by doubling the distance from the appliance to the farthest wall to obtain the maximum room size.
For hotels with 501 to 1000 rooms 2 percent of the rooms must be equipped with strobes.
Strobes must be installed no further than 100 feet apart down the length of a hallway.
5 intensity dependent upon room size.
It should be obvious that if you follow this method of compliance you will either have an incorrect number of audible appliances or an incorrect number of visible appliances.
I will add if you are sizing boxes for fire alarm devices go big pushing horn strobes into place that could have eight 14 or 12 awg solid conductors connected to it is no joy if the box is tight.